News Center
News Center
Image Name

NEWS

News Center

Methods for Addressing Load-Related Damage in Screw Chillers

2019-09-21 09:08

First, we need to confirm whether it is Compressor The load is burned out or components are worn away; if so, this will inevitably contaminate the refrigerant system, for example with residual… Freezing After oil carbonization, it remains in the piping, and the dryer filter absorbs large amounts of moisture, among other factors. Therefore, if a compressor burns out, the first step is to analyze the root cause: Is it due to quality issues with temperature‑control components such as contactors or overload relays in the control cabinet? Has the setpoint been inadvertently changed or incorrectly adjusted? Is the power supply voltage unstable? Or did the operator fail to follow the prescribed operating sequence?

   Screw rod Chilled water units are primarily used in the chemical industry, ink printing, large-scale energy equipment, concrete mixing plants, and food preservation, Central air conditioning In the industry, chillers are categorized according to their cooling method into air-cooled screw chillers and water-cooled screw chillers. The compressors used in screw chillers are typically original imported units from Taiwan’s Hanbell or Germany’s Bitzer. These compressors employ a highly efficient 5:6 helical rotor design, delivering energy efficiency that is 20–30% higher than conventional models. However, even the best products have a limited service life and may malfunction due to improper operation. So, when a screw chiller’s compressor fails or encounters issues, how should it be addressed?

  If it has been confirmed that the compressor is damaged and completely inoperable, we should proceed with replacing it according to the following steps:

1. Remove the dryer filter and use a temporary detachable connector or a copper pipe fitting to connect to the bypass section.

  2. Inject the cleaning agent into the piping system to flush and circulate; if necessary, replace the cleaning agent and repeat the cleaning process multiple times.

  3. Dry the entire system thoroughly; at this stage, use nitrogen at a pressure of 10 kg/cm² to blow out any residual cleaning agent.

  4. Install a high-quality compressor and a dryer filter, and perform a leak test using nitrogen at a pressure of 10 kg/cm². Once no leaks are detected, vent the remaining nitrogen to the atmosphere through the high-pressure-side angle valve.

  5. Simultaneously evacuate the system from both the high- and low-pressure sides down to 1000 µbar, then inspect all power supplies and electrical control systems.

  6. Add liquid refrigerant, and once the refrigerant charge reaches 80%–90%, start up the system for testing. Note: The compressor must be heated for 2 hours.

  7. Replace the compressor’s refrigeration oil and observe its performance during compressor operation.
 

Leave a message or feedback