Method for Calculating the Heat Transfer Area of a Condenser
2018-09-25 10:47
1. Method for Calculating the Heat Transfer Area of an Air-Cooled Condenser
Refrigeration capacity + compressor motor power / 200–250 = condenser heat-transfer area. For example: (3SS1-1500 compressor), CT = 40°C, CE = −25°C; compressor refrigeration capacity = 12,527 W + compressor motor power 11,250 W = 23,777 W; divided by 230 W/m² yields a air‑cooled condenser heat-transfer area of 103 m².
2. The ratio of the heat transfer area of the water‑cooled condenser to that of the air‑cooled condenser is approximately 1:18 (103 / 18) = 6 m².
The evaporator area is determined based on the compressor’s cooling capacity (obtained by consulting a table that accounts for the evaporation temperature in °C and the correction factor for relative humidity, Δt).
3. Method for calculating cooling capacity: = Temperature difference × Weight / Time × Specific heat × Equipment maintenance factor
For example: There is a blast freezer.
1) Warehouse temperature: -35℃
2) Freezing capacity: 1 t/h
3) Within 2 hours
4) Frozen product (fresh fish)
5) Ambient temperature: 27°C
6) Calculation of insulation board for the equipment maintenance unit: 62℃ × 1000 / (2 × H) × 0.82 × 1.23 = 31,266 kcal/h. The compressor’s evaporating temperature CT can be taken as 40°C; the cooling capacity at CE = 40°C is 31,266 kcal/h.